for flexible Copper cables
The PKC range of end sleeves is manufactured from Tin plated electrolytic Copper with a purity greater than 99,9%.
Designed and developed to reinforce the fine wire strands, when terminating a cable into a connector block.
Technical details
The connectors are manufactured from Copper Cu DHP UNI 5649/1988
(corresponding to: SF-Cu DIN 1787/1973 Cu/b1 NF A 51-050)
Tin plated with a minimum thickness of 3μm.
Main characteristics of the PA6 sleeves:
-
DIELECTRIC STRENGTH (KV/mm) : >16,5
-
VOLUME RESISTIVITY (Ω • cm) : >1013
-
MAX OPERATING TEMPERATURE (°C) : 115-130
-
FLAMMABILITY (UL94) : V2
-
DENSITY (g/cm3) : 1,14
-
WATER ABSORPTION (%) : 1,5
-
BREAKING LOAD (N/mm2) : 77
The connectors can be stored at a minimum temperature not below - 40°C.