The range of Cembre products related to supply demands for control and automation panels is particularly wide
one piece, push-on, without holder
2011/65/EU
Information technology equipment - Safety
Part 1: General requirements
§ 1.7.11 Durability
Compliance is checked by inspection and by rubbing the marking by hand for 15 s with a piece of cloth soaked with water and again for 15 s with a piece of cloth soaked with hexane.
After this test, the marking shall be legible; it shall not be possible to remove marking plates easily and they shall show no curling.
Ed.2 equivalent to VDE 0411-1
Safety indications for electric devices for measurement, control and laboratory use
Part 1: General indications
This regulation requires that both material and the print shall withstand‚ cleaning with chemical agents commonly used in industry.
By rubbing manually by hand, without excessive pressure, for 30 seconds with a cloth soaked in the specific detergent or, if not specifi ed, Isopropyl Alcohol.
This test was created to simulate cleaning with chemical products commonly used on various surfaces.
By wiping with a cloth soaked in 95% Ethanol 30 times and making a visual inspection after every 10 passes.
The standard specifies methods for exposing plastic test samples to liquid chemical agents and for determining changes in characteristics caused by this exposure. It includes the immersion test for 24 hours of the entire surface of the test sample and applies to all solid plastic materials, submitted in the form of printed or extruded materials, plates, pipes, bars or sheets with a thickness greater than 0.1 mm.
The test samples are completely immersed in a test liquid for a specified time and temperature.
Their characteristics are determined before immersion, after removal from the liquid and after drying.
The test methods specified are the following:
The liquids used by Cembre for this test are: Hydrochloric acid, Nitric acid, Hydrofluoric acid
Material | Polycarbonate |
UL94 class | V0 |
Halogen Free | yes |
Silicon free | yes |
Min operating temperature range | -40 °F |
Max operating temperature range | 266 °F |
MG-TDM-01 |
Geometric shape | rectangular clip with rounded corners |
Minimum outside diameter | 0.06 in. |
Maximum outside diameter | 0.13 in. |
Minimum section | 20 AWG |
Maximum section | 15 AWG |
MG-TDM-02 |
Geometric shape | rectangular clip with rounded corners |
Minimum outside diameter | 0.08 in. |
Maximum outside diameter | 0.17 in. |
Minimum section | 17 AWG |
Maximum section | 10 AWG |